70 MVA Roof-delta connection transformer for Shinkansen (Bullet Train)
70 MVA Scott-connection transformer for Shinkansen (Bullet Train)
20 MVA Scott-connection transformer for conventional line

For railways Scott-connection transformer / Roof-delta connection transformer

This transformer converts three-phase power (special high pressure or ultra-high pressure) to two sets of single-phase power supply. Electric railway specific transformer

Contact Us

Product Features

For AC power feeding system for railways, it requires a large capacity single phase AC power supply. However, in Japan, by regulations, it is not allowed to produce single-phase power from a single-phase high-voltage or ultra high-voltage. Therefore, it is necessary to produce single-phase power from a three-phase high-voltage or ultra high-voltage power.
Given above, a special connection transformer has been adopted. This effectively makes 2 sets of single-phase power from the three-phase power without giving the bad effect of voltage fluctuation or three-phase voltage unbalance at the the power-receiving side.

  • Housing-free design by using a soundproof wall for noise reduction
  • Compact design by our electric field strength analysis technology
  • The scott-connection transformer makes a surge arrester unnecessary due to its full insulation design.
  • The roof-delta connection transformer realizes lower energy loss and compact design compared with a conventional modified Woodbridge connection

Applications and Solutions

Scott-connection transformer

This transformer is applied to a neutral non-grounded high-voltage power network (equal or less than 11 kV to 154 kV ).

Roof-delta connection transformer

This transformer is applied to a neutral grounded ultra high-voltage power network (187 kV or less).

Specifications

Roof-delta connection transformer

Item Rated specification
Application For power feeding a Shinkansen train
Type Oil immersed self-cooling type (with a soundproof wall)
Rated capacity 70MVA
Rating type 300% 2 min
Rated primary voltage 220kV
Connection Roof-delta connection

154 kV Scott-connection transformer

Item Rated specification
Application For power feeding a Shinkansen train
Type Oil immersed self-cooling type (with a soundproof wall)
Rated capacity 50MVA
Rating type 300% 2 min
Rated primary voltage 154kV
Connection Scott connection