DC power feeding system for railwaysTransformer for Rectifier
Under DC feeding system, this transformer steps down the voltage of AC three-phase power to fit with rectifier input.
Product Features
It uses optimal design to meet with special overload rating requirements including Classes D, E, and S for electric railway load, and realizes compact and light weight design.
We can meet with various requirements according to the substation layout such as radiator package type, radiator separate installation type, and primary and secondary bushing, cable, and bus duct systems.
- Optimal design in combination with rectifier
- Flexibly meeting with the layout requirements
- Application of insulation method according to installation conditions
- High reliability proven by the track records
- Supporting various overload ratings (Class E, Class D, Class S)
- Supporting 6- and 12-phase rectification
- It is possible to support using silicone liquid and palm oil, etc. for the environmental consideration
Applications and Solutions
For the DC feeding system, AC is converted to DC by using the rectifier to produce the DC power supply for electric trains.
The transformer is applied to step down the voltage to fit with the input side of this rectifier.
Specifications
Capacity | 4380/2x2265kVA |
---|---|
Rated voltage | 66kV/2x1200V |
Type of rating | Class D (100% continuous, 150% for 2 hrs, 300% for 1 min.) |
Connection | Δ-Δ-⅄ |
Insulation method | Oil-immersed natural cooling |
Capacity | 2160/2x1120kVA |
---|---|
Rated voltage | 22kV/2x590V |
Type of rating | Class D (100% continuous, 150% for 2 hrs, 300% for 1 min.) |
Connection | Δ-⅄-Δ |
Insulation method | Self-cooled type gas insulated |